Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/17/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/17/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new AC units.
2. Show that the revisions to the mechanical systems comply with Section C403, IECC 2012.
3. Show that the "re-used window" (keynote 24 on sheet a3.0) complies with the current IECC requirements.