Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM01864
Parcel: 13623008V

Address:
3225 S WILMOT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM01864
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
06/17/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/17/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations for the new AC units.
2. Show that the revisions to the mechanical systems comply with Section C403, IECC 2012.
3. Show that the "re-used window" (keynote 24 on sheet a3.0) complies with the current IECC requirements.