Permit Number: T16CM01864
Parcel: 13623008V

Address:
3225 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01864
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/01/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the sequence of operation for the restroom exhaust fan with the electrical plans. The exhaust fan shall operate continuously during the occupied hours for the suite. The lights may be controlled by an occupancy sensor but should be independent from the exhaust fan operation.