Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/01/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
04/01/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the sequence of operation for the restroom exhaust fan with the electrical plans. The exhaust fan shall operate continuously during the occupied hours for the suite. The lights may be controlled by an occupancy sensor but should be independent from the exhaust fan operation. |