Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM01864
Parcel: 13623008V

Address:
3225 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01864
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/18/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The HVAC system supplies air to the restroom continuously during occupied hours but the fan is scheduled to be shut off with the lights when the restroom is unoccuppied. With the fan off, the air supplied to the restroom will not be exhausted. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.]
03/18/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how the waste and vent isometric for LAV-1 and WC-1 will be modified to provide a cleanout for the 4" drain. [Initial comment: Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.]