Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM01864
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/18/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/18/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The HVAC system supplies air to the restroom continuously during occupied hours but the fan is scheduled to be shut off with the lights when the restroom is unoccuppied. With the fan off, the air supplied to the restroom will not be exhausted. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.] |
03/18/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how the waste and vent isometric for LAV-1 and WC-1 will be modified to provide a cleanout for the 4" drain. [Initial comment: Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.] |