Permit Number: T16CM01864
Parcel: 13623008V

Address:
3225 S WILMOT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01864
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/10/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/10/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2012.
03/10/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide branch circuit and panel designations for all new or relocated lighting as required per City of Tucson Commercial Plan Submittal requirements.
Ref: IBC 107.2.1, NEC art. 408.
03/10/2016 ROBERT SHERRY WATER REVIEW Completed
03/10/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.
2. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.
03/11/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/11/2016 STEVE SHIELDS ZONING REVIEW Approved
03/11/2016 MARTIN BROWN FIRE REVIEW Approved