Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM01864
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/10/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/10/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted. Reference: Section 403.2.1 (4), IMC 2012. |
03/10/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide branch circuit and panel designations for all new or relocated lighting as required per City of Tucson Commercial Plan Submittal requirements. Ref: IBC 107.2.1, NEC art. 408. |
03/10/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
03/10/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/10/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03. 2. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012. |
03/11/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
03/11/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
03/11/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |