Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM01837
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/16/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/16/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Submit an appeal to the building official. [Initial comment: Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted (i.e. the fan shall operate whenever air is supplied to the restroom). Reference: Section 403.2.1 (4), IMC 2012.] |