Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM01837
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/10/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 03/10/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide information on the sequence of operation for the restroom exhaust fan to show that all of the air supplied to the restroom will be exhausted (i.e. the fan shall operate whenever air is supplied to the restroom). Reference: Section 403.2.1 (4), IMC 2012. |
| 03/10/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/10/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 03/10/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A02.100; PLAN 04: IT APPEARS DOOR 101 INTO THE ATM DOES NOT MEET THE REQUIREMENTS OF THE IBC SECTION 1005.7.1 FOR ENCROACHMENT INTO THE MEANS OF EGRESS. PLEASE VERIFY. |
| 03/10/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/10/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/10/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/11/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |