Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM01636
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/14/2016 | KEN BROUILLETTE | FIRE | REVIEW | Passed | STATE FIRE MARSHAL REVIEW REQUIRED-OWNED BY PUBLIC SCHOOL |
| 03/30/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. COVER SHEET: PLEASE REVISE THE TITLE NUMBER OF THIS SHEET TO A-CS. 2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE SOIL REPORT JOB NUMBER (792-055) DOES NOT MATCH THE SOIL REPORT JOB NUMBER LISTED ON SHEET S1 (2925JH084-E). PLEASE CLARIFY. 3. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE SOIL REPORT INDICATES THE ALLOWABLE LATERAL SOIL PRESSURE FOR DRILLED PIERS IS 400 PSF/FOOT, WHILE THE SHEET S1 (AND CALCULATION SHEET 1) INDICATE 425 PSF/FOOT. PLEASE COORDINATE AND REVISE CALCULATIONS AS REQUIRED. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 04/01/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |