Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM01636
Parcel: 10603148A

Address:
125 W YAVAPAI RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM01636
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2016 KEN BROUILLETTE FIRE REVIEW Passed STATE FIRE MARSHAL REVIEW REQUIRED-OWNED BY PUBLIC SCHOOL
03/30/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. COVER SHEET: PLEASE REVISE THE TITLE NUMBER OF THIS SHEET TO A-CS.
2. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE SOIL REPORT JOB NUMBER (792-055) DOES NOT MATCH THE SOIL REPORT JOB NUMBER LISTED ON SHEET S1 (2925JH084-E). PLEASE CLARIFY.
3. SHEET S1; GENERAL STRUCTURAL NOTES (FOUNDATIONS): THE SOIL REPORT INDICATES THE ALLOWABLE LATERAL SOIL PRESSURE FOR DRILLED PIERS IS 400 PSF/FOOT, WHILE THE SHEET S1 (AND CALCULATION SHEET 1) INDICATE 425 PSF/FOOT. PLEASE COORDINATE AND REVISE CALCULATIONS AS REQUIRED.
4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
04/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2016 KROBLES1 OUT TO CUSTOMER Completed