Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM01634
Parcel: 121113250

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01634
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/03/2016 STEVE SHIELDS ZONING REVIEW Approved
03/03/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
03/03/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/03/2016 KEN BROUILLETTE FIRE REVIEW Approved
03/30/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. GENERAL: THE APPEAL FOR THIS PROJECT ALLOWS 40 TOTAL OCCUPANTS (STAFF AND PATIENTS). PLEASE INDICATE ON THE DRAWINGS THE MAXIMUM TOTAL OCCUPANT LOAD OF 40, ADD CALCULATIONS ON THE DRAWINGS FOR PLUMBING FIXTURES REQUIRED AND PROVIDED, AND INDICATE THE APPEAL NUMBER ON THE DRAWINGS.
2. SHEET A1.0; KEYNOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE.
3. SHEET A1.0; FLOOR PLAN: PLEASE INDICATE ONE NEW RESTROOM AS MEN'S, AND ONE AS WOMEN'S. HOW IS THE SHOWER TO BE USED BY BOTH SEXES?
4. SHEET A1.0; FLOOR PLAN: SIGNAGE MUST BE POSTED FOR 40 TOTAL OCCUPANTS PER THE IBC SECTION 1004.3. PLEASE INDICATE ON THE PLAN.
5. SHEET A1.0; FLOOR PLAN: SIGNAGE MUST BE PROVIDED FOR ACCESSIBLE ELEMENTS PER THE IBC SECTION 1110. PLEASE INDICATE THOSE SPECIFIC SIGNS ON THE PLAN.
6. SHEET A1.0; FLOOR PLAN: IS THE NEW SHOWER A TRANSFER TYPE OR ROLL-IN TYPE PER THE ICC/ANSI? THE LOCATION OF THE CONTROLS PER THE ICC/ANSI SECTION 608.4 DEPENDS ON THAT DETERMINATION.
7. SHEET A1.0; CODE ANALYSIS: THE OCCUPANCY TYPE IS LISTED AS B (GENERAL BUSINESS). PLEASE REVISE.
8. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/30/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change This activity represents a change of use from mercantile to institutional (I-4); show that adequate ventilation is being provided.
03/30/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Relocate the shower controls per Section 608.4, ICC/ANSI Standard A117.1-2009.
03/30/2016 ROBERT SHERRY WATER REVIEW Reqs Change Acording to Tucson Water, this address can expect water pressure exceeding 80 PSI. Provide a pressure regulating valve listed to ASSE 1003 to limit the water pressure to less than 80 PSI. Reference: Section 604.8, IPC 2012.
03/30/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review