Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T16CM01597
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/22/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET A1.0; TWO HOUR EXTERIOR WALL DETAIL: PER THE IBC SECTION 705.5, THE REQUIRED FIRE RESISTANCE RATING OF EXTERIOR WALLS WITH A FIRE SEPARATION DISTANCE OF 10' OR LESS SHALL BE RATED FOR EXPOSURE FROM BOTH SIDES. THE ASSEMBLY INDICATED SHOWS PROTECTION ON ONE SIDE ONLY. PLEASE REVISE TO A DIFFERENT ASSEMBLY. 2. SHEET S2.1: PLEASE INCLUDE A LETTER INDICATING THE CHANGES TO ALL SHEETS, PROVIDING A DETAILED EXPLANATION ON EACH CHANGE. 3. SHEET S2.1; DETAIL 11: PLEASE ADD THE VERBIAGE THAT IS NOT COMPLETED ON THIS DETAIL. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/26/2016 | ARUIZ1 | APPROVAL SHELF | Completed |