Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM01597
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 1; WEST BUILDING WALL: THE REFERENCE USED IN YOUR RESPONSE (IBC 706.3.9) IS NOT VALID IN THE 2012 IBC. PLEASE REVISE. IN ADDITION, THE NEW NOTE ON SHEET A1.0 INDICATES A SEPARATION BETWEEN A 'B' (SHELL SPACE) AND AN 'M' (FRYS) IS REQUIRED TO BE 2 HOURS. WHEN THIS JOB WAS SUBMITTED, THE OCCUPANCY TYPE WAS ASSUMED TO BE A TYPE 'M'. PLEASE CLARIFY THE ASSUMED OCCUPANCY TYPE. THIS WILL HAVE AN IMPACT ON THE FIRE RESISTANCE RATING OF THE NEW WEST WALL. 2. SHEET A1.0; FLOOR PLAN: IF THE NEW WEST WALL IS A FIRE WALL, THE IBC SECTIONS 706.5 (HORIZONTAL CONTINUITY) AND 706.6 (VERTICAL CONTINUITY) MUST BE APPLIED, AND ALL THOSE REQUIREMENTS MUST BE MET. PLEASE VERIFY AND REVISE PLAN AND NOTES AS REQUIRED. 3. PREVIOUS COMMENT 15; STRUCTURAL CALCULATIONS (SHEET 10): IT DOES NOT APPEAR A FLOOR LOAD HAS BEEN ADDED TO THIS SET OF CALCULATIONS FOR BEAM B4. PLEASE VERIFY. 4. PREVIOUS COMMENT 16; STRUCTURAL CALCULATIONS (SHEET 11): IT DOES NOT APPEAR A FLOOR LOAD HAS BEEN ADDED TO THIS SET OF CALCULATIONS FOR BEAM B5. PLEASE VERIFY. 5. PREVIOUS COMMENT 17; STRUCTURAL CALCULATIONS (SHEETS 13 THROUGH 17): PLEASE VERIFY THE FOUNDATION SIZES (FOR ADDED FLOOR LOADING). 6. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 05/03/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/10/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. Ref: Plan Sheet E2.0. #1. Comment from last electrical plan review was not addressed, "Please address the following electrical plan review comment. Also provide a written response. #1.Provide complete panel schedules for panels A, B, & C. Or Delete". No change on electrical plans. Could not locate comment response for electrical in construction documents. If these panels are to remain as shown provide complete panel schedules and show location on the floor plan. #2. Provide plan sheets E1.2, E1.3, E1.4, or delete, or explain notes on plan sheet E1.1, "SEE SHEET E1.2, E1.3, E1.4 FOR ADDITIONAL INFORMATION". Ref: 2012 IBC 107.2.1 |
| 05/20/2016 | ERIC NEWCOMB | ADA | REVIEW | Passed |