Permit Number: T16CM01562
Parcel: 14113008H

Address:
9455 E RITA RD

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM01562
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approv-Cond Requires a review for a right of way permit by codes and permits. Please provide a pdf of the development plan to Steve Tineo in Codes and Permits.
03/17/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Ref: Plan sheet E-4. Available Fault Current at the service shown as 22K, The service is rated at 10K per the one line diagram.
#2. Compliance with sec.801 Tucson /Pima County Outdoor Lighting Code.
IBC sec. 107.2.1, 2011 NEC
03/17/2016 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
03/21/2016 STEVE SHIELDS ZONING REVIEW Passed
03/24/2016 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
04/05/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved LETTER SENT TO RECORDS

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2016 ARUIZ1 OUT TO CUSTOMER Completed