Permit Number: T16CM01561
Parcel: 14042072B

Address:
7060 S TUCSON BL

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T16CM01561
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2016 CLAYTON TREVILLYAN BUILDING-COMMERCIAL REVIEW Completed
03/16/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.Also provide a written response.
#1.Per the Fault Current calc's on plan sheet E4, the available Fault Current at the service is 22k. The 100 Amp service rated pedistal and main breaker shown on the one line diagram should be rated at 22k not 10k as shown.
Ref: IBC sec 107.2.1, 2011 NEC.
03/17/2016 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Approved
03/17/2016 LOREN MAKUS ENGINEERING REVIEW Approved
03/18/2016 STEVE SHIELDS ZONING REVIEW Passed
03/31/2016 FRODRIG2 COMMUNICATIONS REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/07/2016 KROBLES1 OUT TO CUSTOMER Completed