Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM01561
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2016 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
03/16/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments.Also provide a written response. #1.Per the Fault Current calc's on plan sheet E4, the available Fault Current at the service is 22k. The 100 Amp service rated pedistal and main breaker shown on the one line diagram should be rated at 22k not 10k as shown. Ref: IBC sec 107.2.1, 2011 NEC. |
03/17/2016 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved | |
03/17/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
03/18/2016 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
03/31/2016 | FRODRIG2 | COMMUNICATIONS | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/07/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |