Permit Number: T16CM01533
Parcel: 116206300

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T16CM01533
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2020 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show that the proposed 6" diameter scupper is equivalent to the flow capacity of a 4" x 4" rectangular scupper. Reference: Section 1108, IPC 2012 and Sections 1611.1 and 1611.3, IBC 2012.
2. The use of Table 1106.3, IPC 2012 is not an appropriate method for determining the size of a scupper. The table is for determining the size of horizontal storm drainage pipes running full; scuppers are weirs, not pipes and their sizes are hydraulically calculated.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/11/2020 PC_TGUTHEI1 APPROVAL SHELF Passed
09/11/2020 PC_TGUTHEI1 REJECT SHELF Passed
09/11/2020 PC_TGUTHEI1 OUT TO CUSTOMER Completed