Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T16CM01533
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/14/2020 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide calculations to show that the proposed 6" diameter scupper is equivalent to the flow capacity of a 4" x 4" rectangular scupper. Reference: Section 1108, IPC 2012 and Sections 1611.1 and 1611.3, IBC 2012. 2. The use of Table 1106.3, IPC 2012 is not an appropriate method for determining the size of a scupper. The table is for determining the size of horizontal storm drainage pipes running full; scuppers are weirs, not pipes and their sizes are hydraulically calculated. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/11/2020 | PC_TGUTHEI1 | APPROVAL SHELF | Passed |
09/11/2020 | PC_TGUTHEI1 | REJECT SHELF | Passed |
09/11/2020 | PC_TGUTHEI1 | OUT TO CUSTOMER | Completed |