Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T16CM01533
Review Name: COMMERCIAL - NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/03/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Show the plumbing fixtures and drainage fittings installed correctly and in a manner consistent with the Code and the manufacturer's instructions (see M/P5.7 and Unit C2/P2.2). Reference: Section 303.2, IPC 2012. 3. The fixture drain serving an automatic clothes washer shall connect to a fixture branch that is at least 3 inches in diameter. Also, a 2" horizontal branch (not a building drain) can accommodate a maximum of 6 drainage fixture units. Reference: Section 406.2 and Table 710.1 (2), IPC 2012. 4. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (see "General Notes (Water)" which specifies a dual check backflow preventer for this application). The pressure-absorbing devices shall conform to ASSE 1010. Reference: Section 604.9, IPC 2012. 5. Verify that a low-pressure cutoff for the booster pump is provided per Section 606.5.5, IPC 2012. 6. At a minimum, beverage dispensers (e.g. coffee makers) require the use of a backflow preventer that is listed to ASSE 1022. Reference: Section 608.16.10, IPC 2012. 7. Provide a cleanout at the base of each roof drain stack prior to connection to the horizontal storm drain. Reference: Sections 708.3.4 and 1101.8, IPC 2012. 8. Provide accessible cleanouts in the island sink vent system (detail 7/P4.1) to permit rodding of all portions of the vents located below the flood rim of the fixture. Reference: Section 916.3, IPC 2012. 9. Provide a detail showing how the proposed grease interceptor and ejector pump are to be installed. Reference: Sections 1003.2 and 1003.3, as amended by the City of Tucson, IPC 2012 and Section 107.2.1, IBC 2012. 10. Verify that adequate access will be provided to the proposed gravity grease interceptor for service and maintenance (i.e. can a pumper truck reach the interceptor). Reference: Section 1003.10, IPC 2012. 11. Provide the roof drain calculations (i.e. show the total area drained by each roof drain). Include the effect of any vertical walls that can divert rainfall onto the roof and show the area of the balconies or decks that are combined with the roof drainage piping. Reference: Section 1106, IPC 2012. |
| 03/03/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Water meters and reduced pressure zone backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Contact Richard Sarti, New developments Manager, (520) 837-2215, to coordinate access with Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf |
| 03/07/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the font size used on the drawings to a minimum height of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 2. Explain how the required horizontal and vertical fire separations and the rated egress corridors are to be maintained with the proposed routing of the exhaust ducts (dryer, bathroom, EF-7, EF-8, and EF-9). Reference: Sections 708.3 and 711.3, IBC 2012. 3. Clarify the routing of the exhaust duct running from the grease interceptor room to exhaust fan EF-8. The duct does not appear on the third floor plan and on the second floor plan it is called out as connecting to EF-7. Reference: Section 107.2.1, IBC 2012. 4. Provide mechanical ventilation for the residential areas of the building per Table 403.3, IMC 2012. Reference: Section 401.2 and 403.3, IMC 2012 and Sections R402.4.1.2 and R403.5, IECC 2012. 5. A dressing room is not a storage room; revise the calculations for the two dressing rooms served by HP-1 and HP-2 using a listed occupancy classification from Table 403.3, IMC 2012 that most closely resembles the actual use of the spaces (e.g. sports locker room, retail dressing room, etc.). Reference: Section 403.3, IMC 2012. 6. Show how the dryer installation complies with Section 504.5, IMC 2012. 7. Provide listing information for the clothes dryers to show that the proposed dryer exhaust ducts are sized correctly. Reference: Sections 304.1 and 504.6.1, IMC 2012. 8. Provide signage indicating the total equivalent length of the concealed dryer exhaust duct. Reference: Section 504.6.5, IMC 2012. 9. Provide the proposed types and quantities of chemicals that will be stored or used in the pool equipment room. Clarify how the exhaust flow rate was determined for the room. Reference: Section 502.8, IMC 2012. 10. All of the combustion air for the pool heater appears to be coming from inside of the building. Show how the size of each of the two openings to the hallway complies with the requirements of Sections 304.5.3.1 and 304.10, IFGC 2012. 11. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012, and Section 312.1, IMC 2012. 12. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (i.e. coordinate the wall types shown on the plans with the wall types used in the COMcheck analysis). Reference: Section C303.1, IECC 2012, as amended by the City of Tucson. 13. Clarify how the "Additional Efficiency Package Requirements" noted in COMcheck (C406, IECC 2012) is to be accomplished for the commercial portions of the building. The envelope and mechanical compliance certificates note that reduced lighting power is to be used to comply with Section C406 but the interior lighting compliance certificate calls for high efficiency HVAC to be used to comply with Section C406. Reference: Sections C101.4.6 and C401.2, IECC 2012. 14. Show how the residential portions of the building envelope are to be constructed to limit the air leakage per the requirements of Section R402.4, IECC 2012. |
| 03/14/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: 160 S. Avenida Del Convento T16CM01533 Building Plan (1st Review) TRANSMITTAL DATE: March 14, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Per Tentative Plat, S04-53, General note 34 a development package is required. Until the required development package has been submitted and approved Zoning cannot approve the building plan. 3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 03/15/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments, also provide a written response. #1. Provide for tamper resistant receptacles in the dwelling units as required per NEC. #2. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for exterior lighting. The tucson outdoor lighting code can be downloaded from www.tucsonaz.gov/pdsd. #3. Indicate the main circuit breaker sizes and types in all the multi-meter packs feeding the dwelling units. #4. Provide for a listed fire block system for all the conduit or cable penetrations through any fire rated walls or floors. #5. What are the heat and smoke detectors at the top of the elevator shafts connected to? Ref: IBC sec.107.2.1, 2011 NEC |
| 03/18/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 03/18/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | ARCHITECTURAL COMMENTS: 1. SHEET G0.01: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE CODES, REGULATIONS, AND STANDARDS. 2. SHEET G0.01; APPLICABLE CODES: PLEASE REMOVE THE 2012 IRC FROM THIS LIST. 3. SHEET G0.01; APPLICABLE CODES: PLEASE INDICATE THE 2009 EDITION OF THE ICC/ANSI CODE. 4. SHEET G0.02; PLANS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 5. SHEET G0.02; CODE SUMMARY: PLEASE INCLUDE THE RETAIL OCCUPANCY GROUP TO THE TABLE 503 ON THIS SHEET. 6. SHEET G0.02; CODE SUMMARY: THE TABLE OF ALLOWABLE BUILDING AREAS (SECTION 506.1) INDICATES THE FIRST FLOOR AND SECOND FLOOR ACTUAL AREAS EXCEED THE ALLOWABLE AREAS. PLEASE VERIFY. 7. SHEET G0.02; CODE SUMMARY (FIRE RESISTANCE RATING REQUIREMENTS): WITH A TYPE IA CONSTRUCTION, TABLE 601 INDICATES PRIMARY STRUCTURAL FRAMES MUST BE THREE HOUR RATED ASSEMBLIES, AND EXTERIOR BEARING WALLS MAY BE RATED PER THE IBC TABLE 602. PLEASE CLARIFY AND REVISE ON THE DRAWINGS AS REQUIRED. 8. SHEET G0.02; CODE SUMMARY (SECTION 510.2): ADD TO THE HORIZONTAL ASSEMBLY THAT THE FIRE RESISTANCE RATING OF THE FLOOR ASSEMBLIES SHALL MEET THE REQUIREMENTS OF THE IBC SECTIONS 420.3 AND 711 WHEN THE FLOOR ASSEMBLY SEPARATES AN R-2 OCCUPANCY FROM A B OR M OCCUPANCY, USE TABLE 508.4. WHERE THE FLOOR ASSEMBLY SEPARATES SLEEPING UNITS IN THE SAME BUILDING, USE SECTION 711.3. REVISE THE RATING AND SECTION REFERENCES AS REQUIRED. 9. SHEET G0.02; CODE SUMMARY (706.1.1): THE DRAWING INDICATES A PARTY WALL/FIRE WALL PER TABLE 706.4 MUST HAVE A FIRE RESISTANCE RATING OF TWO HOURS. THIS PARTY WALL/FIRE WALL REFERENCE IS FOR SEPARATING BUILDINGS OR PORTIONS OF BUILDINGS BECAUSE THE ACTUAL AREAS (PER FLOOR) EXCEED THE ALLOWABLE AREAS. THE FIRST AND SECOND FLOORS EXCEED THE ALLOWABLE AREAS, AND CAN BE SEPARATED FROM THE OTHER FLOORS WITH FIRE WALLS PER THE IBC SECTION 706, AND HORIZONTAL ASSEMBLIES PER THE IBC SECTION 711. PLEASE INDICATE ON THE DRAWINGS IF THIS IS THE SYSTEM THAT WILL BE USED, AND CLARIFY THE AREAS TO BE SEPARATED. 10. SHEET G0.02; CODE SUMMARY: PER THE IBC SECTION 420.2, WALLS SEPARATING SWELLING UNITS, WALLS SEPARATING SLEEPING UNITS, AND WALL SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER OCCUPANCIES IN THE SAME BUILDING MUST BE CONSTRUCTED AS FIRE PARTITIONS (SECTION 708). PLEASE INDICATE ON THE DRAWINGS, AND INCLUDE THE REQUIRED FIRE RESISTANCE RATING PER THE IBC SECTION 708.3. 11. SHEET G0.02; CODE SUMMARY (713.4): PLEASE INDICATE ON THE DRAWINGS SHAFT ENCLOSURES (FIRE BARRIERS) SHALL HAVE OPENING PROTECTION PER THE IBC SECTION 716, OPENING SIZE LIMITATIONS PER SECTION 707.6, AND PENETRATION PROTECTION PER SECTION 714. VERIFY THESE REQUIREMENTS ARE MET. 12. SHEET G0.02: PLEASE PROVIDE THE PLUMBING FIXTURE CALCULATIONS (WATER CLOSETS, LAVATORIES, DRINKING FOUNTAINS, AND SERVICE SINKS) ON THE DRAWINGS. 13. SHEET G0.03; AREA MODIFICATIONS: PLEASE INCLUDE THE RETAIL OCCUPANCY GROUP TO THE AREA MODIFICATIONS CALCULATIONS. 14. SHEET G0.03; CHAPTER 5: PLEASE INCLUDE THE RETAIL OCCUPANCY GROUP TO THE TABLE 503. 15. SHEET G0.06: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 16. SHEET A1.00 (SITE PLAN); SHEET G0.02 (FLOOR PLANS): IT APPEARS THE ENTIRE EXTERIOR WALL ON GRID 2 IS LESS THAN 5' FROM THE PROPERTY LINE, THEREFORE MUST MEET THE TWO HOUR FIRE RESISTANCE RATING PER THE IBC TABLE 602. THE FIRE RESISTANCE RATING NOTES ON SHEET G0.02 INDICATE ONLY THE SOUTH PORTION OF THAT WALL REQUIRING A RATING. PLEASE VERIFY THAT THE NORTH PORTION OF THAT WALL ON GRID 2 MUST ALSO HAVE THE TWO HOUR RATING. 17. SHEET A1.00; SITE NOTE: NOTE 3 INDICATES ALL GRID LINES ARE SET 1 3/8" FROM PROPERTY LINES. THIS WOULD REQUIRE ALL EXTERIOR WALLS TO HAVE A FIRE RESISTANCE RATING PER THE IBC TABLE 602. THIS IS NOT INDICATED ON THE DRAWINGS. PLEASE VERIFY. 18. SHEET A2.00: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES ON THE PLANS. 19. SHEETS A2.00, A2.11, AND NUMEROUS OTHERS: REVISION 1 WAS ADDED ON THESE SHEETS AFTER THE ARCHITECT OF RECORD SEALED AND SIGNED THE DRAWINGS. PLEASE RESEAL THOSE SHEETS, SIGN, AND DATE. 20. SHEET A2.27; FLOOR PLAN: PLEASE PROVIDE AN INVENTORY OF THE QUANTITY AND TYPE OF HAZARDOUS MATERIALS TO BE STORED IN THE POOL EQUIPMENT ROOM, AND HOW THOSE MATERIALS WILL BE STORED. INDICATE ON THE DRAWINGS THE MAXIMUM ALLOWABLE QUANTITIES INDICATED IN THE IBC TABLE 307.1(1) ARE NOT EXCEEDED. 21. SHEETS A3.01, A3.02, A3.03, AND A3.04: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE ELEVATION NOTES. 22. SHEET A3.04; SECTION 1: PLEASE ADD GRID LINES ON THIS SECTION. 23. SHEETS A3.10 AND A4.01 THROUGH A4.08: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE DIMENSIONS. 24. SHEET A4.01; UNIT A1: THIS DOES NOT APPEAR TO BE AN ACCESSIBLE UNIT. WHY ARE CLEAR FLOOR SPACES INDICATED? IS THIS TO BE DESIGNATED AS A TYPE B UNIT? 25. SHEET A4.02; UNIT B1: SEE NOTE 24. 26. SHEET A4.03; UNIT B2: SEE NOTE 24. 27. SHEET A4.04; UNIT C1: SEE NOTE 24. 28. SHEETS A4.05 AND A4.09; UNITS C2 AND B1ALT: ARE THESE ACCESSIBLE UNITS AS REQUIRED PER THE ICC/ANSI SECTION 1003.11.2? PLEASE REVIEW THE ICC/ANSI SECTIONS 603, 604, 607, AND 609 FOR TOILETS AND BATHING ROOMS. REVIEW SECTION 804 FOR KITCHENS AND COUNTER/SINK HEIGHTS. INDICATE ON THE PLANS THE REQUIREMENTS IN THOSE SECTIONS ARE MET. 29. SHEET A4.06; UNIT C2ALT: SEE NOTE 24. 30. SHEET A4.07; UNITC3: SEE NOTE 24. 31. SHEET A4.08; UNIT C4: SEE NOTE 24. 32. SHEET A7.03: IS THE SECOND ELEVATOR SIMILAR TO THIS ELEVATOR? NO SHEET WAS FOUND FOR VERTICAL CIRCULATION OF THE SECOND ELEVATOR. PLEASE VERIFY. 33. SHEET A8.01; WALL SECTIONS: PLEASE ADD A REFERENCE NOTE TO THIS SHEET FOR LOCATING THE VARIOUS WALL TYPES ON THE DRAWINGS. 34. SHEET A8.01; WALL TYPES 9, 10, 12, AND 14: THESE WALLS INDICATE 4 HOUR FIRE RESISTANCE RATINGS. WHERE ON THIS BUILDING ARE FOUR HOUR WALLS REQUIRED? 35. SHEET A8.01; WALL TYPES: PLEASE INDICATE A U.L. LISTING NUMBER ON THIS SHEET FOR ALL RATED WALLS. 36. SHEET A8.01; WALL TYPES: ARE ALL WALL TYPES INDICATED ON THIS SHEET USED ON THIS PROJECT? PLEASE REMOVE THOSE TYPES THAT ARE NOT APPLICABLE. 37. SHEET A8.02; FLOOR TYPES 2 AND 5: PLEASE INDICATE A U.L. LISTING NUMBER ON THIS SHEET FOR ALL RATED FLOORS. 38. SHEET A8.03; DETAILS 1A, 1B, 2, 3, 5, 6, AND 9: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 39. SHEET A8.04; DETAILS 1, 3, 6, AND 8: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE. 40. SHEET A8.06; DETAILS 2 AND 5: PLEASE REVISE THE SCALE AS LISTED. 41. SHEET A8.09; DETAIL 6: THE HEIGHT OF THE KITCHEN COUNTER WILL VARY BETWEEN TYPE A UNITS AND TYPE B UNITS PER THE ICC/ANSI CHAPTER 10. PLEASE INDICATE THE DIFFERENT REQUIREMENTS ON DETAIL 6, AND ON THE INTERIOR ELEVATIONS ON SHEETS A4.01 THROUGH A4.09. 42. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE BUILDING MUST BE EQUIPPED THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH THE IBC SECTION 903.3.1.1. 43. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE BUILDING MUST HAVE A MANUAL FIRE ALARM AND SMOKE ALARMS THAT MEET THE REQUIREMENTS OF THE IBC SECTION 907.2.9. 44. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE REQUIREMENTS FOR TYPE A UNITS PER THE IBC SECTION 1107.6.2 AND THE ICC/ANSI SECTION 1003 ARE MET. INDICATE THE REINFORCEMENT LOCATIONS (DIMENSIONS) FOR THE WATER CLOSET AND SHOWER GRAB BARS PER THE ICC/ANSI CHAPTER 6, AND LIST COUNTER HEIGHTS, COUNTER WIDTHS, AND CLEAR FLOOR SPACE PER THE ICC/ANSI SECTION 1003. LIST THE TOTAL NUMBER OF UNITS IN THIS COMPLEX, AND THE REQUIRED NUMBER OF TYPE A UNITS. 45. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE REQUIREMENTS FOR TYPE B UNITS PER THE IBC SECTION 1107.6.2 AND THE ICC/ANSI SECTION 1004 ARE MET. INDICATE THE REINFORCEMENT LOCATIONS (DIMENSIONS) FOR THE WATER CLOSET AND SHOWER GRAB BARS PER THE ICC/ANSI CHAPTER 6, AND LIST COUNTER HEIGHTS, COUNTER WIDTHS, AND CLEAR FLOOR SPACE PER THE ICC/ANSI SECTION 1004. LIST THE TOTAL NUMBER OF UNITS IN THIS COMPLEX, AND THE REQUIRED NUMBER OF TYPE B UNITS. 46. GENERAL: PLEASE VERIFY ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 406.5 IN AN OPEN PARKING STRUCTURE OR THE REQUIREMENTS OF THE IBC SECTION 406.6 IN AN ENCLOSED PARKING STRUCTURE ARE MET. 47. GENERAL: PLEASE VERIFY ON THE DRAWINGS A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED PER THE IBC SECTION 1007.8 FOR ELEVATOR LANDINGS AT EACH FLOOR. 48. GENERAL: PLEASE VERIFY ON THE DRAWINGS SIGNAGE IS PROVIDED PER THE IBC SECTIONS 1007.9 AND 1007.10. 49. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. STRUCTURAL REVIEW: 50. SHEET S1.0 (STRUCTURAL NOTES); FOUNDATIONS: NOTE 1 INDICATES A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PLEASE PROVIDE ONE COPY OF THAT REPORT FOR REVIEW. 51. SHEET S1.0 (STRUCTURAL NOTES); GENERAL (DESIGN LOADS): PLEASE INCLUDE THE DEAD LOAD OF THE PODIUM SLAB IN THE DESIGN LOADS. 52. SHEET S3.4 (FRAMING PLAN); SHEET S5.2 (PLAN 271): THE ENLARGED PLAN ON SHEET S5.2 INDICATES COLUMN SUPPORTS FOR THE POOL FRAMING AT GRIDS 4 AND F.9, GRIDS 4 AND G.7, GRIDS 4.2 AND F.9, AND GRIDS 4.2 AND G.7. COLUMNS ARE ALSO INDICATED ON GRID 4 NORTH OF GRID G.7 AND ON GRID 4.2 NORTH OF GRID F.9. THE FRAMING PLAN ON SHEET S3.4 INDICATES THOSE SAME COLUMNS ON GRIDS 4 AND G.6, ON GRID 4 NORTH OF GRID G, ON GRID 4.2 NORTH OF GRID G, AND ON GRIDS 4.2 AND G.7. PLEASE REVIEW THE FRAMING PLANS AND STRUCTURAL CALCULATIONS TO COORDINATE THE FRAMING AT THE POOL LEVEL AND AT THE THIRD AND FOURTH FLOORS. 53. SHEETS S3.8 AND S3.9; ELEVATORS: THE ELEVATORS INDICATE A W18X15 HOIST BEAM. PLEASE REVISE THE BEAM SIZE. 54. STRUCTURAL CALCULATIONS; SHEET 373: THE BEAM DB3-p HIGH (AT THE FOURTH FLOOR) INDICATES A W14X22 ON THE PLAN (SHEET S3.6), WHILE THE CALCULATION INDICATES A W14X26 MIN. PLEASE VERIFY. 55. GENERAL: AT THE POOL AREA (271/S5.2), PLEASE VERIFY ALL COLUMN LOCATIONS INDICATED ON SHEETS S3.0, S3.2, S3.4, AND S3.6 ARE COORDINATED. REVISE THE DRAWINGS AND STRUCTURAL CALCULATIONS AS REQUIRED. 56. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 03/21/2016 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | Several of the notes on the IBC Code Review indicate that this building may be have a NFPA 13R designed fire sprinkler system. Please clarify that only a NFPA 13 system will be installed. This is based on IBC 506.3 that requires a NFPA 13 system if needed for area increase. Code sheet G0.03 does not indicate any type of fire alarm system for the Group R-2 Occupancy. Sheet E2.6 indicates that card readers will be used on egress doors in the stairways. Are these doors to be locked from the egress side? Please indicate compliance with Section 1008.1.9.11. Please indicate that standpipes will be provided per Section 905.3.1 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/13/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |