Permit Number: T16CM01514
Parcel: 10306092G

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T16CM01514
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/01/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/01/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/01/2016 ROBERT SHERRY WATER REVIEW Passed
03/08/2016 KEN BROUILLETTE FIRE REVIEW Reqs Change Please provide additional details regarding amounts of hazardous materials and/or flammable liquids, gasses on site. Refer to chapters 50, 57, and 58 of the 2012 International Fire Code for maximum allowable quantities and methodology for storage of said materials. Clarify intentions as to how IFC requirements will be met.
03/21/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/24/2016 STEVE SHIELDS ZONING REVIEW Passed
03/24/2016 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/31/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET 1; SHEET INDEX: SHEET 8 IS LISTED IN THE INDEX AS PIPING PROFILE FOR EW-010A, WHILE THE SHEET TITLE INDICATES PIPING PROFILE FOR EW-009A. PLEASE CLARIFY.
2. SHEET 11; BUILDING SECTION C: THE STRUCTURAL CALCULATIONS INDICATE FOOTINGS MUST BEAR AT 1'-6" DEPTH FOR A 1500 PSF ALLOWABLE BEARING PRESSURE. THIS SECTION INDICATES A 12" MINIMUM DEPTH. PLEASE REVISE.
3. SHEET 11 (FLOOR PLAN); WELL EW-009A ELEVATIONS; WELL EW-010A ELEVATIONS: THE FLOOR PLAN INDICATES A NORTH ARROW, BUT NONE OF THE WELL ELEVATIONS COORDINATE WITH THAT ALIGNMENT. PLEASE INDICATE A NORTH ARROW ON THE PLAN FOR EACH WELL.
4. GENERAL: PLEASE ATTACH A COMPLETE SET OF STRUCTURAL GENERAL NOTES TO EACH SET.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/04/2016 ARUIZ1 OUT TO CUSTOMER Completed