Permit Number: T16CM01487
Parcel: 12601003C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01487
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/29/2016 STEVE SHIELDS ZONING REVIEW Approved
02/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide ventilation calculations.
02/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide specifications and an installation detail for the water heater.
2. Clarify the installation of the grease interceptor; install per manufacturer's instructions.
3. Provide metering faucets for the lavatories. The faucets shall operate for at least 10-seconds and dispense no more than 0.25 gallons of water per cycle.
02/29/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/29/2016 ROBERT SHERRY WATER REVIEW Completed
02/29/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/29/2016 KEN BROUILLETTE FIRE REVIEW Approved
03/07/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved