Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM01425
Parcel: 13313006N

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01425
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify keynote 1 on sheet P1; is the existing building sewer 4" or 3"? Reference: Section 706.2, IPC 2012.
2. Finish the notes on sheet P.1; six of the detail call-outs are labeled as "XXX" and one keynote is labeled as "X" (4?).
3. The plumbing specification for the P-1 lavatory supplies calls out a Watts L111 thermostatic mixing valve which is an obsolete product and no longer listed. Detail 204 calls out a thermostatic mixing valve that is currently listed. Also, clarify the desired temperature for the tempered water. Reference: Sections 303.4, 607.1.2, and 613.1, IPC 2012.
4. Verify that the pressure-balanced shower valve for the handicapped shower is listed to ASSE 1016. Reference: Sections 424.3 and 424.5, IPC 2012.
5. If the shower does not have a pre-fabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 417.5.2, IPC 2012.
6. Clarify where the P-9 plumbing fixtures are located and provide a specification. Reference: Section 107.2.1, IBC 2012.
03/07/2016 ROBERT SHERRY WATER REVIEW Completed
03/08/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The Avian Ward (A116) requires mechanical exhaust and return from this room is not allowed. Clarify how the local wall switch for the fan will insure that the room is constantly exhausted. Reference: Footnote b, Table 403.3, IMC 2012 and Section 403.2.1 (3), IMC 2012.
03/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET C.1; APPLICABLE CODES: PLEASE ADD THE 2009 ICC/ANSI A117.1 FOR ACCESSIBILITY.
2. SHEET C.1; CODE REVIEW (PLUMBING REQUIREMENTS): PER THE IBC SECTION 2902.2.1, TWO FAMILY/ASSISTED USE TOILET FACILITIES ARE PERMITTED WITH NO REQUIREMENT TO BE IDENTIFIED FOR EXCLUSIVE USE BY EITHER SEX. PLEASE INDICATE THIS ON THE DRAWINGS.
3. SHEET A.1; FLOOR PLAN: KEYNOTE 5 WAS NOT LOCATED ON THE PLAN. PLEASE VERIFY.
4. SHEET A.1; FLOOR PLAN: KEYNOTE 16 IS INDICATED IN TWO LOCATIONS ON THE PLAN, BUT IS NOT LISTED IN THE KEYNOTES. PLEASE VERIFY.
5. SHEET A.2; FLOOR PLAN: PER THE IBC SECTION 2902.3.1, THE ROUTE TO THE PUBLIC TOILET FACILITIES SHALL NOT PASS THROUGH KITCHENS, STORAGE ROOMS, OR CLOSETS. ALL ROUTES SHALL COMPLY WITH THE ACCESSIBILITY REQUIREMENTS OF THE IBC. PLEASE VERIFY THESE REQUIREMENTS ARE MET.
6. SHEET A.2; FLOOR PLAN: PER THE IBC SECTION 2902.4, THE PUBLIC TOILET FACILITIES SHALL BE DESIGNATED BY A LEGIBLE SIGN, READILY VISIBLE, AND COMPLY WITH THE IBC SECTION 1110 FOR ACCESSIBILITY. PLEASE VERIFY ON THE DRAWINGS THOSE REQUIREMENTS ARE MET.
7. SHEET A.2; FLOOR PLAN: PER THE IBC SECTION 2902.4.1, DIRECTIONAL SIGNAGE INDICATING THE ROUTE TO PUBLIC FACILITIES SHALL BE POSTED IN ACCORDANCE WITH THE IBC SECTION 3107. PLEASE VERIFY ON THE DRAWINGS THOSE REQUIREMENTS ARE MET.
8. SHEET A.3; ENLARGED PLAN 1: NOTE 2 INDICATES A 40' X 48' CLEARANCE. PLEASE CHANGE THESE TO INCHES. WHERE IS THIS CLEAR SPACE INDICATED IN THE ICC/ANSI?
9. SHEET A.3; ENLARGED PLANS 1 AND 2: NOTE 5 INDICATES A 60" X 60" CLEARANCE AREA. WHERE IS THIS CLEAR SPACE INDICATED IN THE ICC/ANSI?
10. SHEET A.3 (ENLARGED PLAN 3); SHEET A.5 (DETAIL 1): PER THE ICC/ANSI SECTION 904.3.2, THE PORTION OF THE COUNTER SURFACE SHALL BE A MINIMUM OF 30" IN LENGTH AND A MAXIMUM OF 36" IN HEIGHT. PLEASE INDICATE THIS ON THE ENLARGED PLAN.
11. SHEET A.3; ENLARGED PLAN 3: PLEASE REMOVE THE ENLARGED PLAN KEYNOTES NOT USED.
12. SHEET A.3; ENLARGED PLAN 3: PER THE ICC/ANSI SECTION 904.3.2, A 30" X 48" CLEAR FLOOR SPACE MUST BE PROVIDED FOR A FORWARD APPROACH. PLEASE REVISE THE PLAN NOTE 2.
13. SHEET A.3; WALL TYPES: INDICATE HOW THE TOP WALL BRACE IS CONNECTED TO THE PARTITION WALL AND TO THE STRUCTURE ABOVE. INCLUDE THE BRACE SIZE (STUD) AND CONNECTION QUANTITY AND SIZE.
14. SHEET A.5; DETAILS 3 AND 4: PLEASE VERIFY THE DIMENSIONS FOR THE COUNTER HEIGHTS ABOVE THE FLOOR.
15. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Indicate conduit, conductor feeder sizes and types for new panel 'B'.Ref: plan sheet E5.