Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM01398
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/26/2016 | MARTIN BROWN | FIRE | REVIEW | Passed | Array 4A on existing roof does not appear to meet centerline axis pathways required in 2012 International Fire Code, section 605.11.3.3.2 (2). Please clarify on plans and with response letter. |
| 02/26/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/18/2016 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 03/21/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/24/2016 | CPIERCE1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 03/24/2016 | CPIERCE1 | OIP | REVIEW | Passed | |
| 03/25/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEETS S3 THROUGH S9; DRILLED PIER SCHEDULE: THE DEPTHS OF THE DRILLED PIERS VARY ON THE VARIOUS FRAMING PLANS, AND ON SOME DO NOT AGREE WITH THE STRUCTURAL CALCULATIONS. PLEASE VERIFY AND COORDINATE. 2. GENERAL: PLEASE PROVIDE A WRITTEN RESPONSE TO THE REVIEW COMMENT. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2016 | ARUIZ1 | OUT TO CUSTOMER | Completed |