Review Details: COMMERCIAL - TI
Permit Number - T16CM01371
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/11/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The windows scheduled on sheet A3 do not indicate what the U-value and SHGC are or that they are to be NFRC-certified. If this information is not presented on the window schedule, use the default values from Tables C303.1.3 (1) and C303.1.3 (3), IECC 2012 for the window U-factor and SHGC in COMcheck. [Initial comment: Show how the alterations to the building comply with the current energy code.] |
| 03/11/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/11/2016 | ROBERT SHERRY | WATER | REVIEW | Completed |