Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM01371
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/25/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/25/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Show how the alterations to the building comply with the current energy code. 2. Show that the building has adequate heating capacity to maintain a room temperature of 68 degrees Fahrenheit on a design day of 32 degrees Fahrenheit. 3. Show how the building has been provided with ventilation. |
| 02/25/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/25/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 02/25/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET G1; BUILDING CODE INFORMATION: THE BUILDING CODE INFORMATION INDICATES 2278 SF, WHILE THE SITE PLAN ON THIS SHEET INDICATES 2085 SF. PLEASE CLARIFY. 2. SHEET G1; BUILDING CODE INFORMATION: THE OCCUPANT LOAD IS LISTED AT 46. THE ACTUAL LOAD SHOULD BE 1372/30 + 486/300 = 45.73 + 1.62 = 48. PLEASE REVISE. 3. SHEET G1; BUILDING CODE INFORMATION: THE IBC TABLE 1021.2(2) SHOULD BE REVISED TO TABLE 1015.1 FOR THE NUMBER OF REQUIRED EXITS. 4. SHEET G1; BUILDING CODE INFORMATION: THE TRAVEL DISTANCE IS LISTED AS 200' MINIMUM. PER THE TABLE, IT SHOULD BE 250' MAXIMUM. PLEASE REVISE. 5. SHEET A1; ROOF AND GROUND FLOOR PLANS: A DOUBLE LINE IS INDICATED ON THE WALL SEPARATING ROOMS 100 AND 101. PLEASE INDICATE ON THE PLANS IF THIS IS A NEW OPENING. 6. SHEET A3; ENLARGED RESTROOM PLAN: PLEASE INDICATE ON THE PLAN THE DIMENSION FROM THE WALL TO THE EDGE OF THE LAVATORY MEETS THE ICC/ANSI FIGURE 604.3. 7. SHEET A3; RESTROOM ELEVATIONS: PLEASE INDICATE AND LOCATE THE TOILET PAPER DISPENSER PER THE ICC/ANSI SECTION 604.7. 8. SHEET S3; SPECIAL INSPECTIONS: IT IS INDICATED THAT A FIELD WELDING INSPECTION IS REQUIRED. WHERE ARE THESE LOCATED? 9. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 3411.4.2 ARE MET. 10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/25/2016 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | Show the size of the existing water meter and verify the presence of a reduced pressure backflow preventer. |
| 02/25/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Show how hot water is being provided to the service sink and tempered water is being providd to the lavatory. |
| 02/25/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/26/2016 | MARTIN BROWN | FIRE | REVIEW | Approved |