Permit Number: T16CM01371
Parcel: 117023550

Address:
948 N MAIN AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01371
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/25/2016 STEVE SHIELDS ZONING REVIEW Approved
02/25/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Show how the alterations to the building comply with the current energy code.
2. Show that the building has adequate heating capacity to maintain a room temperature of 68 degrees Fahrenheit on a design day of 32 degrees Fahrenheit.
3. Show how the building has been provided with ventilation.
02/25/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/25/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/25/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET G1; BUILDING CODE INFORMATION: THE BUILDING CODE INFORMATION INDICATES 2278 SF, WHILE THE SITE PLAN ON THIS SHEET INDICATES 2085 SF. PLEASE CLARIFY.
2. SHEET G1; BUILDING CODE INFORMATION: THE OCCUPANT LOAD IS LISTED AT 46. THE ACTUAL LOAD SHOULD BE 1372/30 + 486/300 = 45.73 + 1.62 = 48. PLEASE REVISE.
3. SHEET G1; BUILDING CODE INFORMATION: THE IBC TABLE 1021.2(2) SHOULD BE REVISED TO TABLE 1015.1 FOR THE NUMBER OF REQUIRED EXITS.
4. SHEET G1; BUILDING CODE INFORMATION: THE TRAVEL DISTANCE IS LISTED AS 200' MINIMUM. PER THE TABLE, IT SHOULD BE 250' MAXIMUM. PLEASE REVISE.
5. SHEET A1; ROOF AND GROUND FLOOR PLANS: A DOUBLE LINE IS INDICATED ON THE WALL SEPARATING ROOMS 100 AND 101. PLEASE INDICATE ON THE PLANS IF THIS IS A NEW OPENING.
6. SHEET A3; ENLARGED RESTROOM PLAN: PLEASE INDICATE ON THE PLAN THE DIMENSION FROM THE WALL TO THE EDGE OF THE LAVATORY MEETS THE ICC/ANSI FIGURE 604.3.
7. SHEET A3; RESTROOM ELEVATIONS: PLEASE INDICATE AND LOCATE THE TOILET PAPER DISPENSER PER THE ICC/ANSI SECTION 604.7.
8. SHEET S3; SPECIAL INSPECTIONS: IT IS INDICATED THAT A FIELD WELDING INSPECTION IS REQUIRED. WHERE ARE THESE LOCATED?
9. GENERAL: PLEASE INDICATE ON THE DRAWINGS THE REQUIREMENTS OF THE IBC SECTION 3411.4.2 ARE MET.
10. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/25/2016 ROBERT SHERRY WATER REVIEW Reqs Change Show the size of the existing water meter and verify the presence of a reduced pressure backflow preventer.
02/25/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Show how hot water is being provided to the service sink and tempered water is being providd to the lavatory.
02/25/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/26/2016 MARTIN BROWN FIRE REVIEW Approved