Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T16CM01318
Parcel: 12410008C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01318
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
03/15/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed