Permit Number: T16CM01318
Parcel: 12410008C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01318
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2016 STEVE SHIELDS ZONING REVIEW Approved
02/23/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/23/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/23/2016 LOREN MAKUS ENGINEERING REVIEW Approved
02/23/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1.0; BUILDING CODE REVIEW (OCCUPANT LOAD): THE CALCULATED 70 OCCUPANCY LOAD IS APPROPRIATE FOR THIS USE.
2. SHEET A1.0; BUILDING CODE REVIEW (EXITS): THE DRAWING INDICATES FOUR EXITS ARE PROVIDED, BUT ONLY TWO ARE SHOWN ON THE PLAN. PLEASE CLARIFY.
3. SHEET A1.0; BUILDING CODE REVIEW (PLUMBING FIXTURES): WITH AN OCCUPANCY LOAD OF 70 (35 MALE AND 35 FEMALE), TWO WATER CLOSETS ARE REQUIRED FOR EACH SEX, ONE LAVATORY FOR EACH SEX, ONE SERVICE SINK, AND ONE HIGH/LOW DRINKING FOUNTAIN. PLEASE REVISE THE FIXTURE COUNT INDICATED. ADDITIONAL RESTROOMS MAY BE NEEDED IF THE REQUIREMENTS OF THE IBC SECTION 2902.3.2 ARE NOT MET.
4. SHEET A2.0; FLOOR PLAN: THE URINALS IN THE WOMEN'S RESTROOM ARE NOT CODE COMPLIANT. CLEARANCE IS REQUIRED (30" X 48") FOR AN ACCESSIBLE URINAL, AND THE DOORS DO NOT ALLOW THAT CLEAR SPACE. PLEASE VERIFY.
5. SHEET A2.0; FLOOR PLAN: IN THE MEN'S RESTROOM, A PARTITION (WITH A DOOR) BETWEEN THE WATER CLOSET AND THE URINAL IS REQUIRED, AS WELL AS A PARTITION BETWEEN THE URINAL AND THE LAVATORY.
6. SHEET A2.0; FLOOR PLAN: IN THE MEN'S RESTROOM, PLEASE VERIFY THE WATER CLOSET AND URINAL ARE ACCESSIBLE WITH THE PARTITIONS INCLUDED.
7. SHEET S1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. PLEASE REVISE THE NOTES.
8. GENERAL (STRUCTURAL): PLEASE PROVIDE STRUCTURAL CALCULATIONS AS REQUIRED.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/23/2016 ROBERT SHERRY WATER REVIEW Completed
02/23/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Clarify the size of the RPBP; it is 1-1/4 on sheet P1.0 but 3" on P2.0.
2. Provide partitions in the men's restroom per Section 405.3.5, IPC 2015 unless it is to be a single occupancy restroom.
02/23/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/24/2016 MARTIN BROWN FIRE REVIEW Approved