03/17/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM01286
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

STRUCTURAL PLANS:

1. Provide a beam sized with appropriate load carrying capacity, R301.1. The 4"x 10" beam at the center of the new garage will not carry the load a gypsum board ceiling. It only meets the limit of an open rafter roof assembly.

SECTIONS - DETAILS - NOTES:

1. Clarify the need for the 5/8" gypsum board ceiling in compliance with R309.2 that appears on sheet #3. Table R302.6 only requires this application when habitable rooms are above the garage.
2. Show a ½" gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R302.6 without window opening.

ELECTRICAL PLANS:

1. Show (new or existing) at least one GFCI receptacle outlet in the garage, E3901.9 & E3902.2.
2. Show at least one wall switch controlled light in the attached garage, E3903.3.