Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM01206
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S.1 (HIP ROOF PLAN); STRUCTURAL CALCULATIONS (PAGE A9): THE CALCULATIONS INDICATE MEMBERS M9, M10, M12, AND M13 TO BE 1/2" DIAMETER RODS, WHILE THE ROOF PLAN INDICATES A 3/8" DIAMETER CABLE. IS THIS THE SAME MEMBER? PLEASE VERIFY AND REVISE AS REQUIRED. 2. SHEET S.1 (DETAIL 4); STRUCTURAL CALCULATIONS (PAGE F2): THE CALCULATIONS DO NOT INDICATE THE ANCHOR BOLT LENGTH REQUIRED, AND DETAIL 4 INDICATES 16" LONG ANCHOR BOLTS. PLEASE PROVIDE THE CALCULATION. 3. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/30/2016 | RBENT1 | APPROVAL SHELF | Completed |
| 03/30/2016 | RBENT1 | OUT TO CUSTOMER | Completed |
| 03/30/2016 | RBENT1 | REJECT SHELF | Completed |