Permit Number: T16CM01130
Parcel: 133148170

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM01130
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/31/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Revise the architectural background to show the walls. Reference: Section 107.2.1, IBC 2012.
3. Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. toaster). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.2.2, IMC 2012.
03/31/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not resolved, the expiration date for the seal is required on all plumbing sheets. [Initial comment: Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Comment not addressed. [Initial comment: Revise the architectural background to show the walls. Reference: Section 107.2.1, IBC 2012.]
3. Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.
4. Provide a direct connection for the hand sink. Reference: Sections 301.3 and 802.1, IPC 2012.
5. Provide an indirect waste pipe for the prep sink. Reference: Section 801.2, IPC 2012.
6. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. The 30-compartment sink is currently shown with direct connections to the sanitary drain. Reference: Sections 801.2 and 802.1.8, IPC 2012.
7. A dishwasher may not discharge through a hydromechanical grease interceptor. Verify how the discharge from the dishwasher can be accommodated with the Pima County Regional Wastewater Reclamation Department. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.
04/12/2016 CPIERCE1 BUILDING-COMMERCIAL REVIEW Completed