Permit Number: T16CM01081
Parcel: 14029037D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM01081
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2016 MARTIN BROWN FIRE REVIEW Reqs Change Please provide manufacurers cut sheets on oven, and provide a narrative describing type of work performed under hood. Of particular interest is the type of fumes/gases being exhausted by the hood.
02/26/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the installed weight of the hoods and exhaust ductwork. Provide structural details to show how the hoods and exhaust ductwork are to be connected to the building structure. Reference: Section 302.1, IMC 2012.
2. Provide a description of the process that will be occurring in the oven along with the Material Safety Data Sheets for the materials involved in the process. If any hazardous, combustible, explosive or flammable vapors are produced by the process, provide the concentration and health-hazard rating of the exhaust stream. Reference: Sections 502.1 and 510.1, IMC 2012.
3. Show the distance of the exhaust termination from building openings, combustible walls, roofs, and the property lines. Reference: Section 501.3.1, IMC 2012.
4. Provide the quantities of materials that will be stored to support this process and the storage location. Reference: Section 107.2.1, IBC 2012.
03/04/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET GI001; CODE REVIEW (ALLOWABLE AREA): THE IBC SECTION 506.3 ALLOWS A 300% INCREASE IN ALLOWABLE AREA FOR A SINGLE STORY BUILDING. THIS WOULD ALLOW 3(23,000) + 23,000 = 92,000 SF. PLEASE REVISE.
2. SHEET GI001; CODE REVIEW (OCCUPANCY): IS THIS A TYPE B (BUSINESS) OCCUPANCY? THE ADDITION OF THIS OVEN MIGHT INDICATE AN F-2 (SEE THE IBC SECTION 306.3).
3. SHEET MH102: PLEASE PROVIDE STRUCTURAL CALCULATIONS TO INDICATE THE EXISTING ROOF STRUCTURE CAN SAFELY SUPPORT THE NEW HOOD AND DUCTWORK.
4. SHEET MH102: PLEASE PROVIDE DETAILS ON THE DRAWINGS INDICATING HOW THE NEW HOOD AND DUCTWORK ARE SUPPORTED FROM THE EXISTING ROOF STRUCTURE.
5. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/15/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Denied While the electrical review for the current submittal is approved, due to the potential modifications necessary to address comments associated with the reviews of other disciplines the electrical workflow is denoted as denied in order to verify that those modifications will not adversely impact the electrical review.