02/16/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a complete panel schedule for panel 'B' and Fault current available at all service and downstream equipment. Include fault current ratings of the equipment. Grounding to include Bld. steel. Gas, Water.
IBC 107.2.1. 2011 NEC