Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T16CM01009
Parcel: 125070880

Address:
2509 E 5TH ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T16CM01009
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2016 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T16CM01009
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide two sets of updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL COMMENTS:

1. Provide consecutive sheet numbers on each construction drawing, R106.1.1.

SITE PLAN:

1. Indicate the location of sewer lines from property line to building, R106.1.1. Show the point of connection of proposed lines to the service lines for verifying correct sizes and necessary upgrades.

STRUCTURAL PLANS:

1. Provide rafter sizes and spacing (sheet #4) in compliance with Table R802.5.1, or show an I-joist series for determining performance compliance, R301.1

SECTIONS - DETAILS:

1. Show a garage frame wall supported with a foundation stem for achieving the 6" clearance between framing and ground (R317.1 item 5) or show a ramp at the vehicle door opening.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing (closed cell spray or rigid board tight to the roof sheathing), R806.5. This condensation control provision is necessary for code compliance, and may be a single layer of air-impermeable insulation, or layered with batt insulation for achieving the total required roof R-value. The layer of air-impermeable insulation may be placed on either side of the roof sheathing.

PLUMBING PLANS:

1. Show accessibility for servicing the water heater, IPC 502.5.
2. Show an individual accessible water supply shut off for each dwelling unit, P2903.9.1.
3. Show building drain pipe size and a two-way cleanout at the building exterior, at 100' intervals and at change of direction exceeding 135 degrees, P3005.2.
4. Relocate underground gas piping from beneath buildings, G2415.14.

MECHANICAL PLANS:

1. Provide an equipment specification list including the MINI-SPLIT tonnage capacity, M1302.1.

ELECTRICAL PLANS:

1. Clarify the feeder size for the 100A subpanel. The panel schedule shows #2 wire size and the notate shows #4 wire size. The feeder protection with appropriate breaker rating must be located at the supply side of the feeder; therefore the 100A breaker and #2 wire size is correct and the #4 notation is not.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/18/2016 RBENT1 OUT TO CUSTOMER Completed