04/18/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A100; EGRESS PLAN: THIS PLAN INDICATES THE TRAVEL DISTANCE TO THE EXIT ON THE NORTH WALL. THIS DOOR REQUIRES AN OCCUPANT TO PASS THROUGH A KITCHEN, WHICH IS NOT ALLOWED PER THE IBC SECTION 1014.2(4). FORTUNATELY, THE EXITS ON THE SOUTH AND EAST WALLS MEET THE SEPARATION DISTANCE OF THE IBC SECTION 1015.2.1(2). PLEASE REVISE THE EGRESS PLAN.
2. COVER SHEET: THE OCCUPANT LOAD IS STATED TO BE 103, BUT THE CODE ANALYSIS FOR REQUIRED EXITS AND PLUMBING FIXTURES IS BASED ON AN OCCUPANT LOAD OF LESS THAN 50. PLEASE EXPLAIN. SEE THE IBC SECTION 1004.1.2 FOR OCCUPANCY LOAD VARIATIONS.
04/18/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Restroom exhaust fan sequence of operation unchanged. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan shall operate whenever supply air is being delivered to the restrooms, even if the lights are off). Reference: Section 403.2.1 (4), IMC 2012.]
2. Provide the size of the dryer exhaust duct. [Initial comment: Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, 504.4 and, 504.6, IMC 2012.
04/18/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment.
#1. The addition of a seperate exhaust fan switch only, ( restrooms ), does not satisfy mechanical requirements. See mechanical.
2012 IBC 107.2.1
04/18/2016 ROBERT SHERRY WATER REVIEW Completed
04/18/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The specified faucet does not appear to be a metering faucet capable of limiting the quantity of dispensed water to a maximum of 0.25 gallons per metering cycle. [Initial comment: Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucets will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-03.]
2. Explain how backflow protection is provided for the water connection to the simple syrup mixer (#6). Clarify how the air gap fitting (Watts model 909AG) for the BFP (Watts model 719) is to be installed. [Initial comment: Appliances (e.g. espresso machines, ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3, and 608.16.10, IPC 2012.]
3. Show the location of the required cleanouts on the drawings. [Initial comment: Provide cleanouts sized for the nominal size of pipes that they serve up to 4-inches. Reference: Section 708.7, IPC 2012.]
4. Comment not addressed. [Initial comment: Hand sinks in the food preparation area are allowed to connect to the sanitary waste system instead of the grease waste system only if each sink has a sign posted above it stating, "HANDWASH SINK ONLY! NO FOOD PREPARATION OR DISHWASHING ALLOWED." Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.]
04/19/2016 MARTIN BROWN FIRE REVIEW Reqs Change Sheet G1 indicates an occupant load of 103, non-sprinklered. 2012 IFC, section 903.2.1.2 indicates sprinklers are required. Additionally, not a "B" occupancy.
05/03/2016 RBENT1 ZONING REVIEW Needs Review