Permit Number: T16CM00863
Parcel: 13316024N

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T16CM00863
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2016 ROBERT SHERRY WATER REVIEW Reqs Change Per Tucson Water, the water pressure range for this address will be greater than 80 PSI. Provide a pressure reducing valve conforming to ASSE 1003 or CSA B356 with a strainer to reduce the water pressure to not less than 80 PSI. Reference: Section 604.8, IPC 2012.
02/19/2016 CPIERCE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/25/2016 MARTIN BROWN FIRE REVIEW Reqs Change Per 2012 IFC and IBC, section 1008.1.10, panic hardware required on door 107A (sheet A2.0)
02/26/2016 LOREN MAKUS ENGINEERING REVIEW Approved
03/01/2016 AROMERO4 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
03/01/2016 AROMERO4 ZONING REVIEW Needs Review
03/01/2016 AROMERO4 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2016 AROMERO4 OUT TO CUSTOMER Completed