Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T16CM00861
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/11/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/14/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/16/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The revision shows two 2" PVC pipes being used to draw a vacuum on the safety cabinet. What will be stored in the cabinet - flammable or corrosive chemicals (i.e. how will the fumes affect the PVC)? How will the exhaust system be balanced? |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/23/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |