| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/24/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. ( 2/24/16 ) #1. Signage not added as indicated per response to last plan review comment #1. #2. The response to comment #2 does not correlate with the notes on the plans in reference to the generator. Original plan sheet E1.1 note 2.6 indicates "exact ratings as shown on the drawings" ? Plan sheet E4.0 does not reflect this information as mentioned per response. Electrical plan review comments ( 2 / 8 / 16 ) Please address the following electrical plan review comments. #1. Provide for sign as required per. NEC art.702.7. #2. Include electrical spec's for the generator, voltage, amps, size in KW. Ref: IBC sec 107.2.1, 2011 NEC |