Permit Number: T16CM00861
Parcel: 13323371A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM00861
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. ( 2/24/16 )
#1. Signage not added as indicated per response to last plan review comment #1.
#2. The response to comment #2 does not correlate with the notes on the plans in reference to the generator. Original plan sheet E1.1 note 2.6 indicates "exact ratings as shown on the drawings" ? Plan sheet E4.0 does not reflect this information as mentioned per response.

Electrical plan review comments ( 2 / 8 / 16 )
Please address the following electrical plan review comments.
#1. Provide for sign as required per. NEC art.702.7.
#2. Include electrical spec's for the generator, voltage, amps, size in KW.
Ref: IBC sec 107.2.1, 2011 NEC
02/24/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed