Permit Number: T16CM00861
Parcel: 13323371A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00861
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2016 STEVE SHIELDS ZONING REVIEW Approved
02/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Two new hoods are being installed. Describe what is being exhausted, the balancing criteria for each hood, and how the discharge for the hoods complies with the requirements of Section 501.3.1, IMC 2012.
2. Exhaust from the flammable-contents cabinet is being combined with the exhaust from the grossing hood. How will balancing be done? Verify that EF-2 is listed for this type of exhaust and that the termination of the exhaust complies with Section 501.3.1, IMC 2012.
02/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/05/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/05/2016 ROBERT SHERRY WATER REVIEW Completed
02/05/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/08/2016 KEN BROUILLETTE FIRE REVIEW Approved
02/08/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments.
#1. Provide for sign as required per. NEC art.702.7.
#2. Include electrical spec's for the generator, voltage, amps, size in KW.
Ref: IBC sec 107.2.1, 2011 NEC