Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM00861
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Two new hoods are being installed. Describe what is being exhausted, the balancing criteria for each hood, and how the discharge for the hoods complies with the requirements of Section 501.3.1, IMC 2012. 2. Exhaust from the flammable-contents cabinet is being combined with the exhaust from the grossing hood. How will balancing be done? Verify that EF-2 is listed for this type of exhaust and that the termination of the exhaust complies with Section 501.3.1, IMC 2012. |
| 02/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/05/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 02/05/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/05/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/05/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/08/2016 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 02/08/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. #1. Provide for sign as required per. NEC art.702.7. #2. Include electrical spec's for the generator, voltage, amps, size in KW. Ref: IBC sec 107.2.1, 2011 NEC |