Permit Number: T16CM00860
Parcel: 140420780

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00860
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2016 STEVE SHIELDS ZONING REVIEW Approved
02/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide the cooling/heating load calculations for RT-5 and RT-6.
2. Show that the new RT- units comply with the requirements of the IECC 2012 for efficiency and controls.
3. Provide justification for the occupancy rate and the outside air flow rates for the new area.
02/05/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/05/2016 PAUL BAUGHMAN ENGINEERING REVIEW Approved
02/05/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/05/2016 ROBERT SHERRY WATER REVIEW Completed
02/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/05/2016 MARTIN BROWN FIRE REVIEW Approved
02/05/2016 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed