Permit Number: T16CM00858
Parcel: 11901042B

Address:
200 E BENSON HY

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T16CM00858
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/05/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the ventilation calculations to show the required exhaust flow rate for the showers.
2. Coordinate the cooling/heating load calculations with the HVAC units being installed.
3. Revise the return for the dining hall to avoid using the egress corridor as a duct.
02/05/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/16/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved