Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T16CM00858
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/05/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the ventilation calculations to show the required exhaust flow rate for the showers. 2. Coordinate the cooling/heating load calculations with the HVAC units being installed. 3. Revise the return for the dining hall to avoid using the egress corridor as a duct. |
02/05/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
02/16/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |