Permit Number - T16CM00829
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/05/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. There was no response to comment #2 from the previous plan review,"#2. Provide compliance with NEC art. 250.32 at the separate structures ( fuel canopies )" |
| 05/09/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Carioca - Shell & 2 Fuel Canopies T16CM00824, T16CM00829 & T16CM00890 Building Plan (2nd Review) TRANSMITTAL DATE: May 9, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The building plans have been reviewed for compliance with DP14-0167 and DP15-0173 and it appears that the plans meet the requirements. 3. The grading plan sheets that are provided within the building plans either need to be the approved set or marked as reference only. 4. Until the building plan has been approved by all PDSD agencies Zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |