Permit Number: T16CM00824
Parcel: 141220280

Address:
9255 S RITA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T16CM00824
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/02/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the roof construction. The Envelope Compliance Certificate on sheet A0.1 calls out an "other" roof with a U-value of 0.011 but the section on sheet A6.0 shows a wood truss roof with R-38 cavity insulation. The use of "other" components requires the submission of supporting documentation to justify the stated U-value. [Initial comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code and presented using COMcheck Envelope Compliance (see M3.0 and E1.0 for examples). Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.]
05/03/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
05/09/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Carioca - Shell & 2 Fuel Canopies
T16CM00824, T16CM00829 & T16CM00890
Building Plan (2nd Review)

TRANSMITTAL DATE: May 9, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed for compliance with DP14-0167 and DP15-0173 and it appears that the plans meet the requirements.

3. The grading plan sheets that are provided within the building plans either need to be the approved set or marked as reference only.

4. Until the building plan has been approved by all PDSD agencies Zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
05/12/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved