Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T16CM00824
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/29/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
05/02/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the roof construction. The Envelope Compliance Certificate on sheet A0.1 calls out an "other" roof with a U-value of 0.011 but the section on sheet A6.0 shows a wood truss roof with R-38 cavity insulation. The use of "other" components requires the submission of supporting documentation to justify the stated U-value. [Initial comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code and presented using COMcheck Envelope Compliance (see M3.0 and E1.0 for examples). Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.] |
05/03/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
05/09/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Carioca - Shell & 2 Fuel Canopies T16CM00824, T16CM00829 & T16CM00890 Building Plan (2nd Review) TRANSMITTAL DATE: May 9, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The building plans have been reviewed for compliance with DP14-0167 and DP15-0173 and it appears that the plans meet the requirements. 3. The grading plan sheets that are provided within the building plans either need to be the approved set or marked as reference only. 4. Until the building plan has been approved by all PDSD agencies Zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
05/12/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |