Permit Number: T16CM00785
Parcel: 10508014E

Address:
4941 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00785
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/11/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
02/11/2016 ROBERT SHERRY WATER REVIEW Completed
02/19/2016 MARTIN BROWN FIRE REVIEW Approved
02/26/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A1; FLOOR PLAN KEYNOTES: NOTE 3 REFERENCES DETAIL 1 ON SHEET A1 FOR A METAL STUD WALL. PLEASE REVISE THE DETAIL REFERENCE.
2. SHEET A1; FLOOR PLAN KEYNOTES: NOTE 11 REFERENCES DETAILS ON SHEET A2 FOR THE ROOF HATCH AND RAILING. PLEASE REVISE THE DETAIL REFERENCE.
3. SHEET A1; FLOOR PLAN KEYNOTES: NOTE 5 INDICATES TO SEE STRUCTURAL FOR NEW STEEL BEAMS. THOSE BEAMS ARE INDICATED ON SHEET A2. PLEASE REVISE THE NOTE.
4. SHEET A1 (FLOOR PLAN); BEAM/COLUMN SCHEDULE: PLEASE MOVE THE BEAM AND COLUMN SCHEDULE TO SHEET A2.
5. SHEET A2; BUILDING SECTION/ROOF FRAMING PLAN/FLOOR FRAMING PLAN: ALL DETAILS/SECTIONS INDICATE SHEET A2. PLEASE REVISE THAT SHEET NUMBER.
6. SHEET A3 (SECTION 11); STRUCTURAL CALCULATIONS: THE FOOTING SECTION INDICATES #3 @ 12" O.C. REINFORCING TOP AND BOTTOM, WHILE THE CALCULATION INDICATES #5 @ 6" O.C. PLEASE COORDINATE.
7. SHEET A3; SECTION 11: A NOTE INDICATES TO SEE STRUCTURAL FOR THE STEEL COLUMN. PLEASE REFERENCE SHEET A2.
8. GENERAL: PLEASE LIST ON THE DRAWINGS MATERIAL SPECIFICATIONS (CONCRETE, REINFORCING, STRUCTURAL STEEL, WELDING, PLYWOOD, STEEL STUDS, ETC.).
9. GENERAL: PLEASE LIST ON THE DRAWINGS DESIGN LOADS (ROOF LL, FLOOR LL, DESIGN WIND SPEED, DESIGN SEISMIC CLASSIFICATION, ALLOWABLE SOIL BEARING, ETC.).
10. STRUCTURAL CALCULATIONS: PLEASE PROVIDE TWO SETS OF STRUCTURAL CALCULATIONS.
11. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/02/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/03/2016 LOREN MAKUS ENGINEERING REVIEW Approved
03/04/2016 STEVE SHIELDS ZONING REVIEW Passed