Permit Number: T16CM00760
Parcel: 129020510

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T16CM00760
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide a complete one line diagram include:
#1. Wiring method for terminations inside the enclosure between the term can and the CT cabinet and meter bases.
#2. Indicate feeder conduit, conductor sizes and types between meter bases, CT cabinet and the enclosure or wireway, AIC ( fault current ) at service equipment, fuse types for service disconnects.
#3. Provide for a complete grounding electrode system, include grounding electrode conductor types and sizes.
#4. Building load calcs. Ref: IBC 107.2.1, 2011 NEC . City of Tucson Commercial Plan Submittal Requirements.