Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T16CM00760
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a complete one line diagram include: #1. Wiring method for terminations inside the enclosure between the term can and the CT cabinet and meter bases. #2. Indicate feeder conduit, conductor sizes and types between meter bases, CT cabinet and the enclosure or wireway, AIC ( fault current ) at service equipment, fuse types for service disconnects. #3. Provide for a complete grounding electrode system, include grounding electrode conductor types and sizes. #4. Building load calcs. Ref: IBC 107.2.1, 2011 NEC . City of Tucson Commercial Plan Submittal Requirements. |