Permit Number: T16CM00688
Parcel: 13101053B

Address:
1255 S SWAN RD

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T16CM00688
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2016 EGALLET1 WWM REVIEW Completed
02/01/2016 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide on the plans, in detail the line side tap location, and verify from the manufacture the method used will not compromise the listings of the electrical equipment. Provide compliance with the 2011 NEC art. 110.3, 690, 705.12.