Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T16CM00577
Parcel: 12310001A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T16CM00577
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/01/2016 MARTIN BROWN FIRE REVIEW Approved
03/03/2016 LOREN MAKUS ENGINEERING REVIEW Reqs Change Development Package must be approved first.
03/08/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET S1.2.0 (LEGEND); SHEET S0.1 (STRUCTURAL NOTES-DESIGN LOADS): THE ROOF LEVEL LOADING LEGEND INDICATES A 40 PSF LIVE LOAD IS APPLIED AT THE ROOF, WHILE THE STRUCTURAL NOTES INDICATE A 20 PSF DESIGN LIVE LOAD. PLEASE CLARIFY AND INDICATE HOW THE 40 PSF WAS DERIVED.
2. SHEET S1.2.0; LEGEND: PLEASE INDICATE HOW THE 250 PSF DESIGN LIVE LOAD AT THE IMAGING FLOOR WAS DERIVED.
3. SHEET S1.3.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INDICATE THE IMAGING FLOOR AREA FROM GRIDS 7 TO 9 AND GRIDS L TO N, WHILE THE LOADING PLAN INDICATES THE IMAGING FLOOR AREA FROM GRIDS 8 TO 10 AND GRIDS K TO N. PLEASE CLARIFY AND REVISE DRAWINGS AND CALCULATIONS AS REQUIRED.
4. SHEET S1.4.0 (LEGEND); SHEET S0.1 (STRUCTURAL NOTES-DESIGN LOADS): THE FOURTH LEVEL LOADING LEGEND INDICATES A 200 PSF LIVE LOAD IS APPLIED AT THE MECHANICAL FLOOR, WHILE THE STRUCTURAL NOTES INDICATE THE MECHANICAL ROOMS DESIGN LIVE LOAD IS 100 PSF. PLEASE CLARIFY AND INDICATE HOW THE 200 PSF LIVE LOAD WAS DERIVED.
5. SHEET S1.4.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS DO NOT INCLUDE THE ROOF TERRACE LOADING SHOWN ON THE LOADING PLAN. PLEASE CLARIFY AND REVISE THE DRAWINGS AND/OR CALCULATIONS AS REQUIRED.
6. SHEET S1.5.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INCLUDE A ROOF TERRACE LOADING THAT IS NOT INCLUDED ON THE LOADING PLAN. PLEASE CLARIFY AND REVISE THE DRAWINGS AND/OR CALCULATIONS AS REQUIRED.
7. SHEET S1.5.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INCLUDE A ROOF/TERRACE AREA BETWEEN GRIDS B TO G AND GRIDS 12 TO 14 THAT IS NOT INCLUDED ON THE LOADING PLAN. PLEASE CLARIFY AND REVISE THE DRAWINGS AND/OR CALCULATIONS AS REQUIRED.
8. SHEET S3.1.1; COLUMN SCHEDULE: COLUMN B.3-13.5 HAS NO BASE PLATE REFERENCE, BUT THE SECTION 4/S4.7 INDICATES A COLUMN BASE PLATE, AND THE CALCULATIONS INDICATE A BASE PLATE DESIGN. PLEASE CLARIFY.
9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
03/11/2016 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Banner Medical Center - Tucson - Expansion & Renovation
T16CM00577
Building Plan (1st Review)

TRANSMITTAL DATE: March 11, 2016

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until Development Package DP16-0027 is approved Zoning cannot approve this building plan.

3. Until the building plan has been approved by all PDSD agencies Zoning cannot approve.

4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2016 KROBLES1 OUT TO CUSTOMER Completed