Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T16CM00577
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/11/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/01/2016 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/03/2016 | LOREN MAKUS | ENGINEERING | REVIEW | Reqs Change | Development Package must be approved first. |
03/08/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S1.2.0 (LEGEND); SHEET S0.1 (STRUCTURAL NOTES-DESIGN LOADS): THE ROOF LEVEL LOADING LEGEND INDICATES A 40 PSF LIVE LOAD IS APPLIED AT THE ROOF, WHILE THE STRUCTURAL NOTES INDICATE A 20 PSF DESIGN LIVE LOAD. PLEASE CLARIFY AND INDICATE HOW THE 40 PSF WAS DERIVED. 2. SHEET S1.2.0; LEGEND: PLEASE INDICATE HOW THE 250 PSF DESIGN LIVE LOAD AT THE IMAGING FLOOR WAS DERIVED. 3. SHEET S1.3.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INDICATE THE IMAGING FLOOR AREA FROM GRIDS 7 TO 9 AND GRIDS L TO N, WHILE THE LOADING PLAN INDICATES THE IMAGING FLOOR AREA FROM GRIDS 8 TO 10 AND GRIDS K TO N. PLEASE CLARIFY AND REVISE DRAWINGS AND CALCULATIONS AS REQUIRED. 4. SHEET S1.4.0 (LEGEND); SHEET S0.1 (STRUCTURAL NOTES-DESIGN LOADS): THE FOURTH LEVEL LOADING LEGEND INDICATES A 200 PSF LIVE LOAD IS APPLIED AT THE MECHANICAL FLOOR, WHILE THE STRUCTURAL NOTES INDICATE THE MECHANICAL ROOMS DESIGN LIVE LOAD IS 100 PSF. PLEASE CLARIFY AND INDICATE HOW THE 200 PSF LIVE LOAD WAS DERIVED. 5. SHEET S1.4.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS DO NOT INCLUDE THE ROOF TERRACE LOADING SHOWN ON THE LOADING PLAN. PLEASE CLARIFY AND REVISE THE DRAWINGS AND/OR CALCULATIONS AS REQUIRED. 6. SHEET S1.5.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INCLUDE A ROOF TERRACE LOADING THAT IS NOT INCLUDED ON THE LOADING PLAN. PLEASE CLARIFY AND REVISE THE DRAWINGS AND/OR CALCULATIONS AS REQUIRED. 7. SHEET S1.5.0 (LOADING PLAN); STRUCTURAL CALCULATIONS: THE CALCULATIONS INCLUDE A ROOF/TERRACE AREA BETWEEN GRIDS B TO G AND GRIDS 12 TO 14 THAT IS NOT INCLUDED ON THE LOADING PLAN. PLEASE CLARIFY AND REVISE THE DRAWINGS AND/OR CALCULATIONS AS REQUIRED. 8. SHEET S3.1.1; COLUMN SCHEDULE: COLUMN B.3-13.5 HAS NO BASE PLATE REFERENCE, BUT THE SECTION 4/S4.7 INDICATES A COLUMN BASE PLATE, AND THE CALCULATIONS INDICATE A BASE PLATE DESIGN. PLEASE CLARIFY. 9. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
03/11/2016 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Banner Medical Center - Tucson - Expansion & Renovation T16CM00577 Building Plan (1st Review) TRANSMITTAL DATE: March 11, 2016 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until Development Package DP16-0027 is approved Zoning cannot approve this building plan. 3. Until the building plan has been approved by all PDSD agencies Zoning cannot approve. 4. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/16/2016 | KROBLES1 | OUT TO CUSTOMER | Completed |