Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T16CM00520
Parcel: 117170010

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T16CM00520
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2016 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 6: TWO EXITS ARE REQUIRED, AND THE SEPARATION OF THE TWO EXITS ON THE NORTH WALL MUST MEET THE IBC SECTION 1015.2.1 (MINIMUM DISTANCE BETWEEN EXITS IS 95'-6"/2 = 47'-9"). THE PLAN ON SHEET a0.2 INDICATES THAT DISTANCE IS 32'-0", WHICH DOES NOT MEET THE CODE REQUIREMENT. IF THE DOOR ON THE SOUTH WALL (THROUGH STORAGE ROOM 110) IS TO BE USED, THIS ROOM CANNOT BE USED FOR STORAGE. THE DOOR SWING, PANIC BAR, AND EXIT LIGHTING MUST ALSO BE REVIEWED FOR THIS EXIT.
01/29/2016 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
01/29/2016 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
02/01/2016 KEN BROUILLETTE FIRE REVIEW Approved