Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T16CM00520
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | Rio Nuevo review is required for any exterior work. |
| 01/22/2016 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). |
| 01/22/2016 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Provide plumbing plans for the new work in the revised restroom (men's or women's - the name changes from sheet to sheet) including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012. 3. Clarify the model of the water heater proposed for the new bar; detail 4/p3.0 calls out a different model than the wqater heater schedule on sheet p0.1. 4. Explain why a sump pump is now needed for the existing floor sink. Clarify the intake of the proposed sump pump and how the discharge of the sump pump is to connect to the existing sanitary waste system. 5. Provide the kitchen drawings referenced in the plumbing fixture schedule. |
| 01/22/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 01/22/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET a0.1; PROJECT DATA: REVISE THE ACCESSIBILITY CODE TO THE 2009 ICC/ANSI A117.1. 2. SHEET a0.1; FIRE RATED CONSTRUCTION: A NOTE INDICATES THE INTERIOR NON BEARING WALLS AND PARTITIONS ARE ONE HOUR RATED WALLS. PLEASE VERIFY AND LIST ON THE DRAWINGS THE U.L NUMBER FOR THOSE WALLS. 3. SHEET a0.2 (CODE PLAN); SHEET a3.0 (FLOOR PLAN): THE MEN'S RESTROOM (111) DOES NOT MATCH ON THESE TWO PLANS. PLEASE COORDINATE THE PLANS. 4. SHEET a3.0; FLOOR PLAN: THE URINAL (NOTE 12) CLEAR FLOOR SPACE IS INDICATED FOR A FORWARD APPROACH, WHICH IS NOT POSSIBLE DUE TO THE CONFINED SPACE. PLEASE REVIEW THE ICC/ANSI SECTIONS 305.7 AND 605, AND REVISE THE DRAWINGS AS REQUIRED. 5. SHEET a3.0; FLOOR PLAN: THE URINAL IN THE MEN'S RESTROOM (111) MUST BE SEPARATED FROM THE SINK WITH A PARTITION PER THE IPC SECTION 405.3.5. PLEASE REVISE. 6. SHEET a3.0; FLOOR PLAN: THE IBC SECTION 1014.2 DOES NOT ALLOW EGRESS THROUGH A KITCHEN OR STORAGE ROOM. BOTH SOUTH WALL EXITS DO NOT MEET THAT REQUIREMENT. ONE OF THESE MUST BE THE REQUIRED SECOND EXIT FOR THIS BUILDING. PLEASE REVISE. AGAIN, THE PLAN ON SHEET a0.2 DOES NOT MATCH THE PLAN SHEET a3.0 FOR EGRESS. 7. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/22/2016 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 01/22/2016 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/25/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/26/2016 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Please provide documentation indicating existing occupant load has not changed from previous C of O. Please indicate which doors have or will have panic hardware. It appears one of your exits travels from light hazard occupancy through a storage area. This is not allowed, please clarify. Verify all required fire protection inspections (sprinklers, 5 year check valve, alarm, exhaust hood suppression system) are current and provide documentation. |