Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T16CM00507
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/02/2016 | KEN BROUILLETTE | FIRE | REVIEW | Completed | |
| 02/02/2016 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 02/03/2016 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 02/10/2016 | PAUL BAUGHMAN | ENGINEERING | REVIEW | Approved | |
| 02/12/2016 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. SHEET S-1: ARE ANY SPECIAL INSPECTIONS FOR HIGH STRENGTH BOLTS OR FIELD WELDING REQUIRED? MANY OF THE MATERIALS LISTED ON SHEET S-1 WILL REQUIRE SPECIAL INSPECTIONS IF THEY ARE USED ON THIS PROJECT. 2. SHEET S-2: ARE THERE ANY NEW FOUNDATION CALCULATIONS TO ENSURE THE EXISTING FOUNDATION CAN SAFELY SUPPORT THE NEW ANTENNA? PLEASE VERIFY. 3. SHEET S-3: ARE THERE ANY NEW STRUCTURAL CALCULATIONS FOR THE EXISTING ANCHOR BOLTS TO ENSURE THE EXISTING BOLTS CAN SAFELY RESIST VERTICAL AND LATERAL LOADINGS? PLEASE VERIFY. 4. GENERAL: PLEASE PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/16/2016 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/09/2016 | STEVE SHIELDS | PLANNING-CITY HALL | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/06/2016 | CPIERCE1 | OUT TO CUSTOMER | Completed |